Multi Mode 24 fibera OM4 Armoured

  • complies with the Construction Products Regulation (CPR) EU No. 305/2011 and reaction to fire requirements according to the harmonized standards EN 50575: 2014+A1: 2016
  • halogen-free sheath 
  • corrugated steel tape armor 
  • central loose tube filled with water blocking gel 
  • tensile elements made of glass yarns 
  • primary protection of 250 μm 
  • suitable for direct burial campus backbone applications, cable channels and cable bridges without the need of additional protection 
  • resistant to mechanical damage, moisture, water, UV radiation, corrosive liquids, also resistant to welding spark 
  • 100% protection against rodents

 

Technical specification

Standard temperature range (installation) -40°C to +70°C
Standard temperature range (operation) -40°C to +70°C
Min. bending radius (installation) 110 mm
Min. bending radius (operation) 110 mm
Max. tensile load (installation) 1000 N (100 kg)
Max. tensile load (operation) 500 N (50 kg)
Outer cable diameter 8,5 mm
Weight 85 kg/km
Number of tubes x number of fibers 1 x 24
Reaction to fire Eca
Fire safety flame retardant, low smoke, zero halogen, non-corrosive

The determination of Reaction to Fire Class Performance of this cable has been performed by Product Certification Body notified by European Commision.